1.5 HP 250 VAC
SPECIFICATIONS
distances in areas with heavy radio frequencies.
Current into any input
20 amps 125 VAC tungsten
Inputs
Low voltage contact:
1.0 amp at 6.3 VAC
High Voltage Contact:
B.
C.
Inputs
1.5 mas
Outputs
277 or 120 VAC plus or minus 10%
(For longer distances, use thicker wire.)
22 VAC open circuit; 20 VAC at 2.5 amps
Copper conductors only
Incandescent lamps to 300 ft.
V.
22 VAC open circuit; 20 VAC at 300 mas
Maximum wire size 10 AWG
A.
17
Torque to 25 pounds/inch
1.0 HP 125 VAC
22 AWG
RCP System Manual
background image
Touch Plate Lighting Controls
Outputs
6.3 VAC at 500mas; 5.8 VAC at 1 amp
22 AWG
20 amps 277 VAC ballast
Maximum allowed in line resistance 100 ohms
7.8 VAC open circuit; 6.3 VAC at 5.5 amps
Large Transformer used in RCP-0012 through RCP-0042
277 or 120 VAC plus or minus 10%
(For longer distances, use thicker wire.)
Relay Specifications
up to 2000 ft. of wire
Do not use twisted pair wire for lengths over 300 ft. Use shielded cable for long
18 AWG
Recommended control wire
Mini Transformer used in RCP-0006:
Recommended lamp wiring:
Low Voltage Circuitry
Transformer
LED's to 1000 ft.
<< < [Pag.20]  

Esta version es la html del arhivo pdf rcp_manual, genearada por domotica.name desde www.touchplate.com

Archivos relacionados:3000pl 5000_5100FP 8000Key ac-ir apd cc cpd8000d cps cps-1011 cps-dmx_spec cps1020 cps1030 cps1031 cps1040 cps1045 cps1050 cps1055 cps1065 cps1090 cps16-24tk cps8-48_manu cps_spec cpsp cpsp_i_manua cpspkey_man cpspkeypad cpx dmx dmx_man dmx_sell_she mcd-r mystique pch1lcx1 ps r8 rcp rcx rpb sceneset ss-100 tk troubleshoot tvr ultra zonez-manual actuadores activethermal airwaysystem automatedceilingregisters coolcomponents easywarmfloor heatizon numinus pcslighting relampit taiserver temperatureguard touchplate warmzone